Permit Number: T12CM00886
Parcel: 119046070

Address:
502 W AJO WY

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T12CM00886
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/13/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
06/14/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
06/14/2012 ROBERT SHERRY WATER REVIEW Denied Comment not resolved; drawing submitted for review shall be properly sealed per the rules of the Arizona Board of Technical Registration. Provide a site drawing showing the size and route of the building water supply along with the location and size of both the water meter and the reduced pressure backflow preventer assembly. Reference: Section 103.2.3, UPC 2006.
06/14/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Comment not resolved. Provide complete energy code compliance calculations for the additions to the building envelope; use the climate zone for Pima County < 4,000 feet. Provide sufficient detail on the drawings to evaluate the energy compliance of the additions to the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections 101.4, 101.4.3, and 104.2, International Energy Conservation Code 2006.
06/18/2012 CPIERCE1 ZONING REVIEW Needs Review