Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM00875
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/06/2012 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 03/06/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 03/06/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 03/06/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 03/06/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET A1.1; WALL TYPE W1 SECTION: INDICATE BRACING AT THE TOP OF THE WALL, INCLUDING BRACE SIZE AND SPACING, AND CONNECTION OF THE BRACING TO THE ROOF STRUCTURE AND THE TOP OF THE WALL. 2. SHEET A1.1; FLOOR PLAN: CONSIDER CHANGING THE NAME OF ROOM 107 (STORAGE). AN ACCESSIBLE RESTROOM AND AN EXIT (ALTHOUGH NOT A REQUIRED EXIT) CAN NOT PASS THROUGH STORAGE. VERIFY. 3. SHEET A1.1; FLOOR PLAN: IS THE DOOR INTO THE STAFF ROOM A DOOR THAT COULD BE LOCKED, THUS DENYING ACCESS TO A RESTROOM? CLARIFY. 4. SHEET A4.1; STANDARD STALL PLAN: INCLUDE THE SINK IN THIS PLAN PER SHEET A1.1. 5. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 03/06/2012 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
| 03/06/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Termination of the excess pressure relief from the water heater over an elevated service sink is not approved location. Reference: Section 504.6 (6), IPC 2006. 2. Provide a design for the mounting shelf for the water heater along with structural calculations to show that the water heater is safely supported. Reference: Sections 106.3.1 and 301.2, IPC 2006. |
| 03/06/2012 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 03/06/2012 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 03/06/2012 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 03/09/2012 | GERRY KOZIOL | WWM | REVIEW | Approved |