Permit Number: T12CM00870
Parcel: 11004345J

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM00870
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/06/2012 TERRY STEVENS ZONING REVIEW Approved
03/06/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved .
03/06/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM00870

1. Provide 2006 Budget Lighting Copliance report.
2. Provide all switching for lighting and fans.
3.Provide a disconnect for WH.

RTMajuta
3/6/12
03/06/2012 ROBERT SHERRY WATER REVIEW Approved
03/06/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
03/06/2012 GERRY KOZIOL WWM REVIEW Approved
03/06/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a riser diagram clarifing the installation of the showers.
2. Provide a detail showing the installation of the ne water heater.
3. Provide a shower valve that is ASSE 1016 listed. Reference: section 418.0, UPC 2006.
03/06/2012 JASON GREEN ENGINEERING REVIEW Approved
03/06/2012 MARTIN BROWN FIRE REVIEW Approved
03/06/2012 ERIC NEWCOMB ADA REVIEW Passed
03/06/2012 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed