Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T12CM00827
Parcel: 137055270

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM00827
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/23/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Clarify the description and location of the floor drain (FD-1) in the Utility room (115); it is scheduled as a floor drain and shown as being located under the clothes washer on the plumbing plan but detail P4/P2 calls it a floor sink, serving as an indirect waste receptor. Indirect waste receptors shall be designed to prevent splashing or flooding and shall be readily accessible for inspection and cleaning. Reference: Sections 103.2.3 and 804.1, UPC 2006.
2. Is the second "SK-3" sink on the plumbing fixture schedule actually "SK-6"? Reference: Section 103.2.3, UPC 2006.
3. Clarify the size of the electric water heater; it is scheduled as 20-gallons on sheet P-2 but keynote 5 on sheet P-1 calls out a 30-gallon water heater. Reference: Section 103.2.3, UPC 2006.
4. Provide a vacuum relief for the storage-type water heater located above the fixture outlets. Reference: Section 608.7, UPC 2006.
5. Horizontal drain lines serving sinks require cleanouts regardless of length. Reference: Section 707.4, UPC 2006.
6. Provide indirect connections for the sterilizer and for the drain of the reduced pressure backflow preventer to the sanitary drain system using an air gap. A "y connection at the sink tailpiece" is not acceptable (keynote 12, P-1). Reference: Section 801.5, UPC 2006.
7. Show the vent for sink SK-3 on the waste and vent schematic. Reference: Sections 901.0 and 910.1, UPC 2006.
8. The upper fixture for a wet vent shall not exceed 2 drainage fixture units (e.g. the washer box). Reference: Section 908.1, UPC 2006.
03/23/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the sequence of operation for the restroom exhaust fans so that all of the air supplied to the new restroom will be exhausted. Reference: Section 403.2.1 (4), IMC 2006.
03/30/2012 GBONILL1 WWM REVIEW Approved