Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/05/2012 | TERRY STEVENS | ZONING | REVIEW | Approved | |
03/05/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise the sequence of operation for the restroom exhaust fans so that all of the air supplied to the new restroom will be exhausted. Reference: Section 403.2.1 (4), IMC 2006. |
03/05/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
03/05/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
03/05/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
03/05/2012 | CPIERCE1 | WWM | REVIEW | Needs Review | |
03/05/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
03/05/2012 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
03/05/2012 | KBROUIL1 | FIRE | REVIEW | Approved | |
03/05/2012 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
03/05/2012 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |