Review Date Reviewer's Name Type of Review Description Status Comments
03/05/2012 TERRY STEVENS ZONING REVIEW Approved
03/05/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the sequence of operation for the restroom exhaust fans so that all of the air supplied to the new restroom will be exhausted. Reference: Section 403.2.1 (4), IMC 2006.
03/05/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
03/05/2012 ROBERT SHERRY WATER REVIEW Approved
03/05/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
03/05/2012 CPIERCE1 WWM REVIEW Needs Review
03/05/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Needs Review
03/05/2012 JASON GREEN ENGINEERING REVIEW Approved
03/05/2012 KBROUIL1 FIRE REVIEW Approved
03/05/2012 ERIC NEWCOMB ADA REVIEW Passed
03/05/2012 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed