Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T12CM00789
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/28/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET A1; FLOOR PLAN: A NOTE INDICATES AN EXISTING DOOR OPENING TO BE ENLARGED TO 14' WIDE X 16' TALL OPENING, AND TO SEE STRUCTURAL FOR THE REVISED OPENING. NO STRUCTURAL DRAWINGS OR CALCULATIONS WERE SUBMITTED WITH THIS REVISION. CLARIFY. |
| 03/28/2012 | RSHERRY1 | WWM | REVIEW | Passed | No new plumbing fixtures. |
| 03/28/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 03/28/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Clarify how the new gas load affects the existing natural gas piping system |
| 03/29/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T12CM00789 1. Sheet E2 is missing, which would show the new circuits and loads. 2. Two new lighting circuits show going to PNL HU1, sheet E2 does not have this panel. Ray Majuta Elect Pln Review PDSD, C of T 3/29/12 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/02/2012 | FERNE RODRIGUEZ | OUT TO CUSTOMER | Completed |