Permit Number: T12CM00789
Parcel: 14029037D

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM00789
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/01/2012 MICHAEL ST. PAUL ZONING REVIEW Approved
03/01/2012 LAITH ALSHAMI ENGINEERING REVIEW Approved
03/02/2012 ROBERT SHERRY WATER REVIEW Approved
03/02/2012 ERIC NEWCOMB ADA REVIEW Passed
03/02/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Specify the minimum resistance (R-value) of the duct (rigid and flexible ducts) insulation to be used on this project. Reference: Section 503.2.7, IECC 2006, as amended by the City of Tucson.
03/02/2012 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
03/02/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. PVC pipe is not approved for water distribution use. Reference: section 605.4, IPC 2006.
2. Provide provision for expansion of the proposed water supply to the new hose bibb.
3. Provide justification for using an indirect waste for the new utility sink. reference: section 802.1, IPC 2006.
03/02/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM00789
Second set of electrical plans missing Sheet E-2
Ray T Majuta
Electrical Pln Review
3/2/12
03/02/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
03/05/2012 KBROUIL1 FIRE REVIEW Approved
03/08/2012 CPIERCE1 WWM REVIEW Needs Review