Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM00789
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/01/2012 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
03/01/2012 | LAITH ALSHAMI | ENGINEERING | REVIEW | Approved | |
03/02/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T12CM00789 Second set of electrical plans missing Sheet E-2 Ray T Majuta Electrical Pln Review 3/2/12 |
03/02/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Specify the minimum resistance (R-value) of the duct (rigid and flexible ducts) insulation to be used on this project. Reference: Section 503.2.7, IECC 2006, as amended by the City of Tucson. |
03/02/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
03/02/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
03/02/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. PVC pipe is not approved for water distribution use. Reference: section 605.4, IPC 2006. 2. Provide provision for expansion of the proposed water supply to the new hose bibb. 3. Provide justification for using an indirect waste for the new utility sink. reference: section 802.1, IPC 2006. |
03/02/2012 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
03/02/2012 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
03/05/2012 | KBROUIL1 | FIRE | REVIEW | Approved | |
03/08/2012 | CPIERCE1 | WWM | REVIEW | Needs Review |