Review Date Reviewer's Name Type of Review Description Status Comments
02/27/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Replot the drawings so that the background is visible.
2. Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that a notation shall be placed beneath the seal, either written, typed, or electronically generated, that provides the day, month, and year of the expiration of current registration. (Effective March 8, 2008).
02/27/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM00671

1. Provide a specification sheet for new chiller, (showing
disconnecting means and overrcurrent protection requirements).
2. Ex fan #6 (new ) is not showing where it is connected.

Ray T Majuta
Elect Plan Review
PDSD,C of Tuc,
Ray.majuta@tucsonaz.gov
03/08/2012 CPIERCE1 PLUMBING-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
03/08/2012 CPIERCE1 OUT TO CUSTOMER Completed