Review Date Reviewer's Name Type of Review Description Status Comments
03/12/2012 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 3-13-12
Activity: T12CM00637
Address: 2017 E Lee St
Applicant: Gus Roumbos

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. Provide keynote number 17 as referenced on sheet A.1.
2. Specify roof cavity insulation installed tight to roof deck or provide attic ventilation, R806.2..
3. Show receptacle outlets along north wall of addition so that no point along the wall (excluding door openings) is more than 6' from a receptacle outlet, E3801.2.
4. At least one wall switch controlled light must be provided at outdoor entrances or exits, E3803.3.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
03/14/2012 CINDY AGUILAR OUT TO CUSTOMER Completed