Permit Number: T12CM00576
Parcel: 12315158C

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T12CM00576
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/23/2012 KBROUIL1 FIRE REVIEW Approved
03/08/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
03/14/2012 ROBERT SHERRY WATER REVIEW Denied Revise the site utility plan to show the location of the water meter and the reduced pressure backflow assembly. Indicate the size of the water meter and the size of the reduced pressure backflow assembly. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code. http://cms3.tucsonaz.gov/sites/default/files/water/docs/backflow-ordinance.pdf
03/14/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
2. All plumbing fixtures and fittings shall be listed or labeled by a nationally-recognized, accredited conformity assessment company (e.g. UL, ETL, UPC, etc). Reference: Section 301.1.1, UPC 2006.
3. Provide information to show that the design of the solar heat exchangers complies with the requirements of Section 603.4.4, UPC 2006 (see also Section 506.4.2, UPC 2006).
4. Provide water pressure and water pipe sizing calculations for the extension to the domestic hot water piping system. Reference: Section 610.1, UPC 2006.
03/14/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
03/16/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved SHEET 7 SHOWS A 240 VOLT RECEPTACLE IN THE FORM OF A 120 VOLT RECEPTACLE, PLEASE CLARIFY AND SHOW WHERE THIS IS BEING FED FROM. PROVIDE THE LOCATION AND LOAD OF THE PANEL

Ray Majuta
Elect Plan Review
3/16/12

Final Status

Task End Date Reviewer's Name Type of Review Description
04/03/2012 CPIERCE1 REJECT SHELF Completed