Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T12CM00576
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/23/2012 | KBROUIL1 | FIRE | REVIEW | Approved | |
| 03/08/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 03/14/2012 | ROBERT SHERRY | WATER | REVIEW | Denied | Revise the site utility plan to show the location of the water meter and the reduced pressure backflow assembly. Indicate the size of the water meter and the size of the reduced pressure backflow assembly. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code. http://cms3.tucsonaz.gov/sites/default/files/water/docs/backflow-ordinance.pdf |
| 03/14/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. 2. All plumbing fixtures and fittings shall be listed or labeled by a nationally-recognized, accredited conformity assessment company (e.g. UL, ETL, UPC, etc). Reference: Section 301.1.1, UPC 2006. 3. Provide information to show that the design of the solar heat exchangers complies with the requirements of Section 603.4.4, UPC 2006 (see also Section 506.4.2, UPC 2006). 4. Provide water pressure and water pipe sizing calculations for the extension to the domestic hot water piping system. Reference: Section 610.1, UPC 2006. |
| 03/14/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 03/16/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | SHEET 7 SHOWS A 240 VOLT RECEPTACLE IN THE FORM OF A 120 VOLT RECEPTACLE, PLEASE CLARIFY AND SHOW WHERE THIS IS BEING FED FROM. PROVIDE THE LOCATION AND LOAD OF THE PANEL Ray Majuta Elect Plan Review 3/16/12 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/03/2012 | CPIERCE1 | REJECT SHELF | Completed |