| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/21/2012 | STEVE SHIELDS | ZONING | REVIEW | Needs Review | |
| 02/21/2012 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 02/21/2012 | CPIERCE1 | FIRE | REVIEW | Needs Review | |
| 02/21/2012 | ENEWCOM1 | ADA | REVIEW | Passed | |
| 02/21/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. GENERAL: PROVIDE A SITE PLAN. 2. GENERAL: PROVIDE TWO SETS OF DRAWINGS AND CALCULATIONS. 3. SHEET S-1; GENERAL STRUCTURAL NOTES: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. 4. SHEET S-1; GENERAL STRUCTURAL NOTES: THE SOIL BEARING NOTES INDICATE A PRESUMPTIVE SOIL BEARING VALUE OF 1500 PSF AT 1' BELOW FINISH GRADE. THE CITY OF TUCSON AMENDMENTS TO THE BUILDING CODE REQUIRE 18" BELOW FINISH GRADE FOR 1500 PSF BEARING. CLARIFY AND REVISE AS REQUIRED. 5. SHEET S-1: IS THE 6" SLAB ON GRADE REINFORCED? VERIFY. 6. SHEET S-2; SECTION E: ARE THERE NO WALL GIRTS AT GRID 1? VERIFY. 7. GENERAL: ALL DEFERRED SUBMITTALS MUST BE APPROVED IN WRITING BY RON BOOSE (BUILDING OFFICIAL) BEFORE THOSE SUBMITTALS WILL BE REVIEWED. RON.BOOSE@TUCSONAZ.GOV. 8. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 02/21/2012 | JASON GREEN | ENGINEERING | REVIEW | Needs Review |