Permit Number: T12CM00451
Parcel: 114516860

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T12CM00451
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/14/2012 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied T12CM00451
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the notated items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2006 International Energy Conservation Code, and Arizona State amendments to the 2006 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
Show corrections and revisions on original tracings or a finished reproducible set. Return two sets along with a set of the first submission for reference. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and notate sheets. (Do not cloud the changes made for comment revisions). Incorporate changes on originals and provide two copied sets for review.

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

PLUMBING PLANS:

1. Provide consistent gas pipe sizes in compliance with connected demand, UPC 1217.2, & Table 12-8. G2413.3 & Table G2413.4(1). The plan notation shows a 125 MBtu water heater and the schedule shows 120,000 Btu demand.

ELECTRICAL PLANS:

1. Show the distance from all fans as not less than.12 feet from the water edge, or in compliance with E4103.4.4 (1) for GFCI and distance limitations.
2. Show the distance from all receptacles as not less than.5 feet from the water edge, E4103.1.5 (E4103.4.5).
3. Show any receptacles within a distance of 10 feet from the water edge on a GFCI circuit, E4103.1.6 (E4103.4.5).
4. Show the distance from the sconce light fixtures to the maximum water level as not less than.7.5 feet and on a GFCI circuit, E4103.4.4, or in compliance with item 2.1 and 2.2 for electrical isolation.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review
09/19/2012 GERRY KOZIOL WWM REVIEW Approved