02/14/2012 ELEIBOL1 ENGINEERING REVIEW Approved No FP affecting proposed generator to be placed on north side of existing main bldg.
02/14/2012 MICHAEL ST. PAUL ZONING REVIEW Approved
02/15/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Electrical Comments:
1. Sheet E2.0 shows a 4 ploe ATS as a part of the new SES2, please explain how the neutral will be connected to the grounded electrode conductor of the 500 KVA Generator
grounding system ? Would not the Neutral to ground connection become isolated by the 4 pole ATS ?

Ray T Majuta
Elect Pln Review
PDSD,C of Tuc
2/15/12