Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T12CM00406
Parcel: 13216600A

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T12CM00406
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/14/2012 ELEIBOL1 ENGINEERING REVIEW Approved No FP affecting proposed generator to be placed on north side of existing main bldg.
02/14/2012 MICHAEL ST. PAUL ZONING REVIEW Approved
02/15/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Electrical Comments:
1. Sheet E2.0 shows a 4 ploe ATS as a part of the new SES2, please explain how the neutral will be connected to the grounded electrode conductor of the 500 KVA Generator
grounding system ? Would not the Neutral to ground connection become isolated by the 4 pole ATS ?

Ray T Majuta
Elect Pln Review
PDSD,C of Tuc
2/15/12
Ray.majuta@tucsonaz.gov
02/15/2012 MARTIN BROWN FIRE REVIEW Approved
02/16/2012 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
02/16/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/23/2012 FERNE RODRIGUEZ OUT TO CUSTOMER Completed