Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/14/2012 | ELEIBOL1 | ENGINEERING | REVIEW | Approved | No FP affecting proposed generator to be placed on north side of existing main bldg. |
02/14/2012 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
02/15/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Electrical Comments: 1. Sheet E2.0 shows a 4 ploe ATS as a part of the new SES2, please explain how the neutral will be connected to the grounded electrode conductor of the 500 KVA Generator grounding system ? Would not the Neutral to ground connection become isolated by the 4 pole ATS ? Ray T Majuta Elect Pln Review PDSD,C of Tuc 2/15/12 Ray.majuta@tucsonaz.gov |
02/15/2012 | MARTIN BROWN | FIRE | REVIEW | Approved | |
02/16/2012 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
02/16/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
02/23/2012 | FERNE RODRIGUEZ | OUT TO CUSTOMER | Completed |