Review Details: REVISION - - 2ND

Permit Number - T12CM00380
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/18/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET S3.0; SHEET A2: IT APPEARS A CHANGE ON SHEET S3.0 HAS TAKEN OUT AN INTERIOR PARTITION WALL AND ADDED NEW COLUMNS AND BEAMS AT THAT LOCATION. WHY DID WE NOT RECEIVE ARCHITECTURAL DRAWINGS INDICATING THOSE CHANGES? PROVIDE.
2. SHEET S3.0: THERE WERE NO STRUCTURAL CALCULATIONS SUBMITTED FOR THE NEW BEAMS AND COLUMNS ADDED WHERE THE INTERIOR PARTITION WAS REMOVED. PROVIDE.
3. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.