Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T12CM00378
Parcel: 11009032B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T12CM00378
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/26/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
04/05/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The submitted roof drainage calculations are incorrect. Table 11-3, IPC 2006 is based upon horizontal conductors running full at a given slope (Table 11-2, IPC 2006, is for vertical conductors only). The design shows a scupper with a weir entry and a short section of a sloping (½" per foot) conductor followed by a steeply sloping conductor; hydraulically, the conductor will exhibit open-channel flow, not full flow. In addition, the plumbing code requires the minimum dimension of a scupper to be 4"; as designed, the scupper has a 4" dimension only at the midpoint of the opening and thus does not meet the code requirement. Submit hydraulic calculations to show that the proposed roof drainage design meets or exceeds the intent of the plumbing code and provides an equivalent level of effectiveness, durability, and safety to the code provisions. Reference: Section 105.4, IPC 2006. [Original comment: Provide roof drainage calculations for OQ-3. Show that the circular scuppers and canales are capable of providing adequate drainage for the roof. Note that Section 1107.3, IPC 2006 requires a minimum opening size of 4" - typically a rectangular opening. Reference: Sections 1101, 1106 and 1107, IPC 2006.]
2. Issue not resolved; see comment number 1.[Original comment: Provide overflow protection for the roof of OQ-3 or provide structural calculations to show that the roof is capable of supporting the additional rain load if the primary roof drains are blocked for any reason. Reference: Sections 1101, 1106 and 1107, IPC 2006 and Section 1611.1, IBC 2006.]
04/10/2013 MARTIN BROWN FIRE REVIEW Approved
04/15/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
04/15/2013 TERRY STEVENS ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
05/01/2013 FERNE RODRIGUEZ APPROVAL SHELF Completed
05/01/2013 FERNE RODRIGUEZ OUT TO CUSTOMER Completed
05/01/2013 CPIERCE1 REJECT SHELF Completed