Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T12CM00376
Parcel: 136100930

Review Status: Completed

Review Details: REVISION - - 2ND

Permit Number - T12CM00376
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/17/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied The submitted natural gas calculations and gas pipe riser diagram are not coordinated. Nine of the nodes shown in the calculations do not exist on the gas riser diagram, eight nodes shown on the diagram are not in the calculations, eleven individual loads (e.g. RTUs) are connected to different nodes, and the diagram shows two "Future 4" loads but no "Future 5" load. [Original comment: Provide natural gas pipe sizing calculations (i.e. provide a revision of sheet P6). Reference: Section 401.8, IFGC 2006.]

Final Status

Task End Date Reviewer's Name Type of Review Description
10/25/2012 CINDY AGUILAR REJECT SHELF Completed