Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T12CM00376
Parcel: 136100930

Review Status: Completed

Review Details: REVISION - - 2ND

Permit Number - T12CM00376
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/27/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
10/01/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
10/02/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
10/02/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide natural gas pipe sizing calculations (i.e. provide a revision of sheet P6). Reference: Section 401.8, IFGC 2006.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/11/2012 FERNE RODRIGUEZ REJECT SHELF Completed