Review Date Reviewer's Name Type of Review Description Status Comments
04/09/2012 MICHAEL ST. PAUL ZONING REVIEW Approved
04/09/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide ventilation calculations and show the balancing date on the drawings. Reference: Section 403.3, IMC 2006, as amended by the City of Tucson.
2. Show the size, route, and termination of the condensate drains.
04/09/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM00355
738 N 5th


1. All lettering and numbering must be 3/32' text min.
2. The 750 MCM AL service entrance conductors limit the service to 384 amps, the new load approx 95 amps, what is the existing load on this service.
R T Majuta
Elect Review
PDSD, C of T
4/9/12
04/09/2012 ROBERT SHERRY WATER REVIEW Approved
04/09/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/09/2012 RSHERRY1 WWM REVIEW Passed No new plumbing fixtures.
04/09/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
04/09/2012 LAITH ALSHAMI ENGINEERING REVIEW Approved
04/09/2012 KEN BROUILLETTE FIRE REVIEW Approved
04/09/2012 ERIC NEWCOMB ADA REVIEW Passed
04/09/2012 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed