Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM00355
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/09/2012 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 04/09/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide ventilation calculations and show the balancing date on the drawings. Reference: Section 403.3, IMC 2006, as amended by the City of Tucson. 2. Show the size, route, and termination of the condensate drains. |
| 04/09/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T12CM00355 738 N 5th 1. All lettering and numbering must be 3/32' text min. 2. The 750 MCM AL service entrance conductors limit the service to 384 amps, the new load approx 95 amps, what is the existing load on this service. R T Majuta Elect Review PDSD, C of T 4/9/12 |
| 04/09/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 04/09/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 04/09/2012 | RSHERRY1 | WWM | REVIEW | Passed | No new plumbing fixtures. |
| 04/09/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 04/09/2012 | LAITH ALSHAMI | ENGINEERING | REVIEW | Approved | |
| 04/09/2012 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 04/09/2012 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 04/09/2012 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |