Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T12CM00335
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/17/2012 | KEN BROUILLETTE | FIRE | REVIEW | Approv-Cond | Provide FD or FSD in rated wall. Could not find on plans. |
| 09/17/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide revised full-sized drawings |
| 09/17/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET A2.00: KEYNOTE 355 INDICATES A NEW OPENING IN AN EXISTING FIRE WALL. PROVIDE A DETAIL ON A FULL SIZE SHEET (NOW SHOWN ON AN 11X17) INDICATING THE NEW OPENING AND REQUIREMENTS FOR THE OPENING THROUGH THE FIRE WALL. 2. FRAMING AT MECHANICAL UNIT/FRAMING AT DUCT OPENING: PLACE THE 8 1/2 X 11 DETAILS ON FULL SIZE SHEETS. INDICATE ON THE PLANS WHERE THESE DETAILS OCCUR. |
| 09/17/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/20/2012 | FERNE RODRIGUEZ | OUT TO CUSTOMER | Completed |