Review Date Reviewer's Name Type of Review Description Status Comments
11/19/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Clarify the revision to the water service to the used car building. The plans now shows two entrances for the water service, one with a shut off valve and no source of water and the other with no shut off valve. Provide a shutoff valve for the new water service to the 2-story building. Reference: Section 606.1, IPC 2006.