Permit Number: T12CM00318
Parcel: 119215970

Address:
1726 W AJO WY

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM00318
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/08/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A1.0; FLOOR PLAN KEYNOTES: NOTE 18 WAS NOT FOUND ON THE PLAN. VERIFY.
2. SHEET A1.0; FLOOR PLAN: PER THE IBC SECTION 1104.5, THE ACCESSIBLE ROUTE TO THE RESTROOMS SHALL NOT PASS THROUGH A STORAGE ROOM. SECTION 1014.2(2) ALLOWS AN EXCEPTION WITH A DEMARCATED AISLE. VERIFY AND PROVIDE ON THE DRAWING.
3. SHEET A3.0; ROOF PLAN KEYNOTES: THESE ARE NOT ROOF PLAN KEYNOTES. REVISE TITLE.
4. SHEET A3.0; ROOF PLAN KEYNOTES: COORDINATE THE KEYNOTES WITH THE NOTES INDICATED ON THE ELEVATIONS.
5. SHEET A4.0; BUILDING FACADE SECTION KEYNOTES: NOTES 4 AND 15 WERE NOT FOUND ON THE SECTION. VERIFY.
6. SHEET A4.0; BUILDING FACADE SECTION KEYNOTES: IS NOTE 7 INDICATED IN THE CORRECT LOCATION ON THE SECTION? VERIFY.
7. SHEET A4.0; BUILDING FACADE SECTION KEYNOTES: COORDINATE THE KEYNOTES WITH THE NOTES INDICATED ON THE SECTION.
8. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
02/08/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
02/08/2012 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
02/08/2012 ROBERT SHERRY WATER REVIEW Approved
02/08/2012 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
02/08/2012 RSHERRY1 WWM REVIEW Passed No new plumbing fixtures.
02/08/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
02/08/2012 ERIC NEWCOMB ADA REVIEW Passed
02/09/2012 JASON GREEN ENGINEERING REVIEW Approved
02/09/2012 STEVE SHIELDS ZONING REVIEW Approved
02/09/2012 MARTIN BROWN FIRE REVIEW Approved