Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T12CM00304
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/08/2012 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 03/02/2012 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1) PROVIDE PANEL SCHEDULES AND LOAD CALCULATIONS TO JUSTIFY DE-RATING THE 200 AMP MAIN BREAKER TO 175 AMPS 2) PROVIDE DETAIL FOR HOW RACKING SYSTEM IS TO BE BONDED TO GROUND, AND WHETHER OR NOT ASSEMBLED SYSTEM IS ELECTRICALLY CONTINUOUS. |
| 03/02/2012 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Approved |