Permit Number: T12CM00304
Parcel: 136150090

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T12CM00304
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/08/2012 MARTIN BROWN FIRE REVIEW Approved
03/02/2012 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Denied 1) PROVIDE PANEL SCHEDULES AND LOAD CALCULATIONS TO JUSTIFY DE-RATING THE 200 AMP MAIN BREAKER TO 175 AMPS

2) PROVIDE DETAIL FOR HOW RACKING SYSTEM IS TO BE BONDED TO GROUND, AND WHETHER OR NOT ASSEMBLED SYSTEM IS ELECTRICALLY CONTINUOUS.
03/02/2012 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
03/08/2012 CINDY AGUILAR REJECT SHELF Completed