Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T12CM00303
Parcel: 132171220

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM00303
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/09/2012 MARTIN BROWN FIRE REVIEW Approved
02/13/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied SHEET A1.1
1. As per table 1015.1, two exits are required for any space with 50 and more occupants. Please calculate the occupants per the 2006 IBC, Table 1004.1.1 for the Administration Area 131 and the Fitness Area 125 and provide additional exits as needed for compliance.
SHEET S1.1
2. For the purpose of assessing additional plan review fees, please provide a written summary to the building official, Mr. Ron Boose, for all deferred submittals.
3. Please provide special inspection certifications as listed.
SHEET E0.0
4. Please provide structural calculations for the light pole foundations.
END OF REVIEW
02/21/2012 ROBERT SHERRY WATER REVIEW Approved
02/21/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The rim elevation of the next upstream sanitary manhole (2496.47') is less than 12" below the first floor elevation (2497.38'). Provide a backwater valve for the first floor building drains per Section 710.1, UPC 2006, as amended by the City of Tucson.
2. The size of a wet vent (Detail C/P2.3) shall be a minimum of one pipe size greater than that required for the drain of the upper fixture. Reference: Section 908.2, UPC 2006.
3. No more than one trap shall be installed on a trap arm (detail A/P2.3). Reference: Section 1001.1, UPC 2006.
4. Clarify the additional floor drain, P-7 shown in detail A/P2.3 but not on the plumbing plan, P1.0. Reference: Section 103.2.3, UPC.
5. Clarify the references to sheet P2.2 in details A/P2.3 and D/P2.3. Reference: Section 103.2.3, UPC.
6. Clarify the design for draining the ice maker; the remarks section of the Plumbing Schedule does not agree with the contents of detail 200. Show how the design complies with the requirements of Sections 804.1, 807.1, and 812.0, UPC 2006. Clarify what the design has to do with a trap primer.
02/22/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the size of the condensate drains in accordance with Section 307.2.1, IMC 2006, as amended by the City of Tucson.
2. The Shoot House, room 119, is not an office; it appears to be an indoor pistol range. Provide an engineering analysis of the ventilation and exhaust requirements for the space. Considering that a NIOSH-certified respirator for lead dust is required during cleanup operations in the room, perhaps the room should not be maintained at a positive pressure with relation to the rest of the building. Reference: Section 403.3, IMC 2006.
03/06/2012 TERRY STEVENS ZONING REVIEW Denied Zoning cannot approve building plan until the site plan has been approved.
03/08/2012 GERRY KOZIOL WWM REVIEW Denied NEED CREDIT EVALUATION DEMO PLAN A0.1 & DEMO PLMB PLAN PD1.0 DO NOT MATCH. NEED TO CLARIFY FOR CREDIT
03/14/2012 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved