Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T12CM00292
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/01/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Comment not resolved; the plumbing plan indicates a 3/4" water meter but the calculations show a 1" water meter. [Original comment: The submitted water pressure calculations do not correspond to the information on the plans. Provide the correct calculations. Reference: Section 106.3.1, IPC 2006.] |
10/03/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | See review for T12CM00290 Ray T Majuta 10/03/2012 |
10/08/2012 | GERRY KOZIOL | WWM | REVIEW | Denied | WAITING FOR CUSTOMER COMMENTS |