Permit Number: T12CM00290
Parcel: 115202610

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T12CM00290
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/01/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
10/03/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM00290 thur 00299
2220 N Silverbell Rd
Silverwood Casitas

1. Sheet E2.1, circuits 18 and 20 show feeding WH #5 30amp disconnect, the panel schedule on Sheet E2.2
shows CB 18 and 20 for disposal and dishwasher. Meanwhile CB 17 and 19 in the panel schedule shows a 20 amp 1 pole on 17 for WH-3 ?

Ray T Majuta
Elect Plan Review
PDSD, C of Tucson
10/03/2012
Ray.Majuta@tucsonaz.gov
10/09/2012 GERRY KOZIOL WWM REVIEW Denied WW IS WAITING FOR CUSTOMER COMMENTS