Permit Number - T12CM00290
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/01/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 10/03/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T12CM00290 thur 00299 2220 N Silverbell Rd Silverwood Casitas 1. Sheet E2.1, circuits 18 and 20 show feeding WH #5 30amp disconnect, the panel schedule on Sheet E2.2 shows CB 18 and 20 for disposal and dishwasher. Meanwhile CB 17 and 19 in the panel schedule shows a 20 amp 1 pole on 17 for WH-3 ? Ray T Majuta Elect Plan Review PDSD, C of Tucson 10/03/2012 Ray.Majuta@tucsonaz.gov |
| 10/09/2012 | GERRY KOZIOL | WWM | REVIEW | Denied | WW IS WAITING FOR CUSTOMER COMMENTS |