Permit Number: T12CM00201
Parcel: 112073910

Address:
2834 E COPPER ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T12CM00201
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/21/2012 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 2-23-12
Activity: T12CM00201
Address: 2834 E Copper St
Applicant: Rusty Knight

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

STRUCTURAL / FRAMING PLAN:
1. Justify rafter spacing. Ripping 2x12 rafters down 3.5" on the narrow side will create the structural equivalence to 2x8 rafters which would need to be spaced no more than 16"o.c. for the proposed span.

SECTIONS - DETAILS:
2. Untreated wood product must be at least 6" above grade or 1" above concrete. Show exterior wall covering height above soil and concrete patio slab, R319.1.4.
3. The proposed roof design includes a fully insulated ceiling cavity. Remove eave venting when no attic space is present.
4. Clarify cross section reference numbers and detail designations.

PLUMBING PLAN:
5. Polybutelene is not an approved water supply piping material -sheet #13.

ELECTRICAL PLAN:
6. Clarify overhead electric drop over detached garage. Overhead conductors must be 8' above the roof, E3504.2.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
02/27/2012 FERNE RODRIGUEZ OUT TO CUSTOMER Completed