Permit Number: T12CM00187
Parcel: 11515051A

Address:
501 W GRANT RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM00187
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/03/2012 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
02/03/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Please provide an approved site plan.
2. Please provide special inspection certifications as per sheet S1.0
SHEET A1.0
3. Please provide toilet facilities in the new addition as per the 2006 IBC, Section 2902.4 and Table 2902.1.
SHEETR A3.0
4. Please provide structural calcs for the roof mounted HVAC unit.
END OF REVIEW.
02/09/2012 JASON GREEN ENGINEERING REVIEW Approved Approved Building only, see DP11-0023 for all site related information and construction details.
02/13/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Clarify which plumbing code is to be used; sheet G1.0 calls out the 2006 IPC and the 2006 IFGC but the gas piping has been sized per the 2006 UPC and the roof drain notes also refer to the UPC. This review has been done using the 2006 UPC.
2. Provide calculations to support the proposed scupper design (the provided calculations are incorrect) or provide structural calculations to show that the roof is capable of supporting the additional rain load. Reference: Sections 1101.11.1 and 1101.11.2.1, UPC 2006, and Section 1611.1, IBC 2006.
3. Clarify the nature of the "water coolers" noted on sheet G1.0. If they are not connected to a permanent source of water, they cannot be considered as substitutes for the required water fountains. Reference: Sections 1109.5 and 2902, IBC 2006.
4. Revise the natural gas load shown for the new AC unit on sheet P1.0 to the manufacturer's rated gas input, not the output of the unit. Reference: Section 1216.2 UPC 2006.
02/13/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. The 2006 IECC is the controlling energy code for commercial buildings, not the 206 IRC (see sheet A1.0).
2. Provide the U-factor and the solar heat gain coefficient (SHGC) for the proposed glass block fenestration. Reference: Section 502.1, IECC 2006.
02/13/2012 ROBERT SHERRY WATER REVIEW Denied Provide a site drawing showing the size and route of the building water supply along with the location and size of both the water meter and the reduced pressure backflow preventer assembly. Reference: Section 106.3.1, IPC 2006.
02/27/2012 TERRY STEVENS ZONING REVIEW Denied Zoning cannot approve the building plan until the development package has been approved.
02/27/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM00187
501 W Grant RD
Office Addition
1. In Panel A, the VA load for the water heater is incorrect, you have a 38 amp load on a 2-pole 30 amp breaker.
2. Indicate on riser diagram if new feeder from Panel A to new Panel B will be copper or Alum.
3. The panel loads for new panel B have not been added to Panel A.
4. Riser Diagram indicates that the existing service is to upgrade to 350 amps, if so provide a new riser diagram showing new service complete with conductors,conduits
grounding system etc.
5. The feeder from Panel A to "E Shut off Box" is incorrect, there is no such size circuit in Panel A.
6. Show location of existing service on plan.
7. The two receptacles shown in the door way to office, one is circuited as #9, what is the other for ?
8. Circuit B-10 and 12-14 not in plan ?

Ray T Majuta
Elect Pln Review
PDSD, C of Tuc
2/28/12
Ray.majuta@tucsonaz.gov
03/05/2012 GERRY KOZIOL WWM REVIEW Passed