Permit Number: T12CM00186
Parcel: 140160080

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM00186
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/25/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
01/25/2012 ERIC NEWCOMB MECHANICAL-COMMERCIAL REVIEW Passed
01/25/2012 ERIC NEWCOMB ELECTRICAL-COMMERCIAL REVIEW Passed
01/25/2012 ENEWCOM1 WATER REVIEW Passed
01/25/2012 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
01/25/2012 ENEWCOM1 WWM REVIEW Passed
01/25/2012 ERIC NEWCOMB PLUMBING-COMMERCIAL REVIEW Passed
01/25/2012 ERIC NEWCOMB ADA REVIEW Passed
01/26/2012 MARTIN BROWN FIRE REVIEW Denied The height of these rackes would acomodate storage above 12' AFF, which becomes "high piled storage". Either include note on cover sheet indicating NO storage above 12', or provide engineered analysis of sprinkler system indicating sprinkler system is capable of supporting high piled storage of your commodities.
02/01/2012 LOREN MAKUS ENGINEERING REVIEW Approved
02/01/2012 TERRY STEVENS ZONING REVIEW Approved