Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM00186
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/25/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 01/25/2012 | ERIC NEWCOMB | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 01/25/2012 | ERIC NEWCOMB | ELECTRICAL-COMMERCIAL | REVIEW | Passed | |
| 01/25/2012 | ENEWCOM1 | WATER | REVIEW | Passed | |
| 01/25/2012 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 01/25/2012 | ENEWCOM1 | WWM | REVIEW | Passed | |
| 01/25/2012 | ERIC NEWCOMB | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 01/25/2012 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 01/26/2012 | MARTIN BROWN | FIRE | REVIEW | Denied | The height of these rackes would acomodate storage above 12' AFF, which becomes "high piled storage". Either include note on cover sheet indicating NO storage above 12', or provide engineered analysis of sprinkler system indicating sprinkler system is capable of supporting high piled storage of your commodities. |
| 02/01/2012 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 02/01/2012 | TERRY STEVENS | ZONING | REVIEW | Approved |