Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 2ND
Permit Number - T12CM00168
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/04/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
01/07/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | A 4" combination drain and vent pipe that is connected to a building drain can accommodate a maximum of 50 drainage fixture units. [Original comment: The combination drain and vent system located on the west side of the building is now receiving the discharge of the gravity grease interceptor and the sanitary drains from the bakery prep and the produce prep areas. Include the fixture units associated with this added load when sizing the combination drain and vent system pipes. Reference: Section 912.3, IPC 2006.] |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
02/06/2013 | CPIERCE1 | REJECT SHELF | Completed |