Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T12CM00168
Parcel: 13409018E

Review Status: Completed

Review Details: REVISION - - 2ND

Permit Number - T12CM00168
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/12/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
12/14/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. GENERAL: SHEETS FXS1 AND FXS2 WERE NOT INCLUDED IN THIS SET OF REVISED DRAWINGS. PROVIDE.
12/19/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide the civil plans associated with the revision to the building sewer. Additional comments may be made after the review of the civil drawings. Reference: Section 106.3.1, IPC 2006.
2. The combination drain and vent system located on the west side of the building is now receiving the discharge of the gravity grease interceptor and the sanitary drains from the bakery prep and the produce prep areas. Include the fixture units associated with this added load when sizing the combination drain and vent system pipes. Reference: Section 912.3, IPC 2006.
12/19/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
12/19/2012 KEN BROUILLETTE FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
12/27/2012 CPIERCE1 REJECT SHELF Completed