Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 2ND
Permit Number - T12CM00168
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
12/12/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
12/14/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. GENERAL: SHEETS FXS1 AND FXS2 WERE NOT INCLUDED IN THIS SET OF REVISED DRAWINGS. PROVIDE. |
12/19/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide the civil plans associated with the revision to the building sewer. Additional comments may be made after the review of the civil drawings. Reference: Section 106.3.1, IPC 2006. 2. The combination drain and vent system located on the west side of the building is now receiving the discharge of the gravity grease interceptor and the sanitary drains from the bakery prep and the produce prep areas. Include the fixture units associated with this added load when sizing the combination drain and vent system pipes. Reference: Section 912.3, IPC 2006. |
12/19/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
12/19/2012 | KEN BROUILLETTE | FIRE | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
12/27/2012 | CPIERCE1 | REJECT SHELF | Completed |