Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T12CM00167
Parcel: 140160080

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM00167
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/24/2012 MICHAEL ST. PAUL ZONING REVIEW Approved
01/24/2012 LOREN MAKUS ENGINEERING REVIEW Approved
01/25/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Needs Review
01/25/2012 LEERAY HANLY MECHANICAL-COMMERCIAL REVIEW Denied PLEASE SHOW SEQUENCE OF OPERATION FOR EXHAUST FAN IN RESTROOMS. EXHAUST TO BE ON WHENEVER A/C IS ON, DOUBLE POLE SWITCH NOTED PP E1 DOES NOT ACCOMPLISH THIS.
01/25/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET T1; ABBREVIATION LEGEND: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE.
2. SHEET S2: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE.
01/25/2012 LEERAY HANLY PLUMBING-COMMERCIAL REVIEW Approved
01/25/2012 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
01/25/2012 ERIC NEWCOMB ADA REVIEW Passed
01/26/2012 CPIERCE1 WATER REVIEW Needs Review
01/26/2012 MARTIN BROWN FIRE REVIEW Approved
01/26/2012 GERRY KOZIOL WWM REVIEW Approved