Permit Number - T12CM00125
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/19/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 01/19/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Coordinate the specifications with the current project. 2. Clarify the material to be used for the distribution of the domestic hot water. 3. Provide piping diagrams for the piping connecting the storage tanks and the boilers; show how the return piping is to be arranged and balanced. 4. Show how the hot water recirculation system is to be controlled. Reference: Section 504.6, IECC 2006. |