Permit Number: T12CM00125
Parcel: 12701003S

Address:
250 N ARCADIA AV

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T12CM00125
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/19/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
01/19/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Coordinate the specifications with the current project.
2. Clarify the material to be used for the distribution of the domestic hot water.
3. Provide piping diagrams for the piping connecting the storage tanks and the boilers; show how the return piping is to be arranged and balanced.
4. Show how the hot water recirculation system is to be controlled. Reference: Section 504.6, IECC 2006.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/07/2012 CPIERCE1 OUT TO CUSTOMER Completed