Permit Number: T12CM00114
Parcel: 11516023B

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T12CM00114
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/02/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
03/02/2012 CPIERCE1 MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide a smoke detector in the return air duct, upstream of any outside air connections. Reference: Section 606.1, IMC 2006.
2. Clarify what is new work.
03/02/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Clarify what is covered under this new revision.
03/02/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Provide Electrical Plans for changes.
Ray T Majuta
Elect Pln Ck
3/2/12

Final Status

Task End Date Reviewer's Name Type of Review Description
03/07/2012 CPIERCE1 OUT TO CUSTOMER Completed