Permit Number: T12CM00114
Parcel: 11516023B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM00114
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/03/2012 DAVID RIVERA ZONING REVIEW Approved
02/03/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Comment not resolved. No architectural calculations have been provided and the proposed truss attachment using a lag screw will result in an unacceptable moment being placed on the bottom chord of the truss. [Original comment: Show how the fan coils are being connected to the building structure and provide calculations to show that the building structure is not being adversely affected. Reference: Section 302.1, IMC 2006.]
02/03/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
02/08/2012 CAGUILA1 WWM REVIEW Needs Review