Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/03/2012 | DAVID RIVERA | ZONING | REVIEW | Approved | |
02/03/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Comment not resolved. No architectural calculations have been provided and the proposed truss attachment using a lag screw will result in an unacceptable moment being placed on the bottom chord of the truss. [Original comment: Show how the fan coils are being connected to the building structure and provide calculations to show that the building structure is not being adversely affected. Reference: Section 302.1, IMC 2006.] |
02/03/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
02/08/2012 | CAGUILA1 | WWM | REVIEW | Needs Review |