Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM00114
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/18/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 01/18/2012 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
| 01/18/2012 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 01/18/2012 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 01/19/2012 | RAY MAJUTA | MECHANICAL-COMMERCIAL | REVIEW | Denied | Show how the fan coils are being connected to the building structure and provide calculations to show that the building structure is not being adversely affected. Reference: Section 302.1, IMC 2006. |
| 01/19/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Clarify the fitting used to connect the back-to-back water closet and mop sink to the drain piping. Reference: section 706.3, IPC 2006. |
| 01/19/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 01/19/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 01/20/2012 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 02/03/2012 | CPIERCE1 | WWM | REVIEW | Needs Review | |
| 02/03/2012 | CPIERCE1 | ZONING | REVIEW | Needs Review |