Permit Number: T12CM00114
Parcel: 11516023B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM00114
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/18/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
01/18/2012 PAUL MACHADO ENGINEERING REVIEW Approved
01/18/2012 ERIC NEWCOMB ADA REVIEW Passed
01/18/2012 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
01/19/2012 RAY MAJUTA MECHANICAL-COMMERCIAL REVIEW Denied Show how the fan coils are being connected to the building structure and provide calculations to show that the building structure is not being adversely affected. Reference: Section 302.1, IMC 2006.
01/19/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Clarify the fitting used to connect the back-to-back water closet and mop sink to the drain piping. Reference: section 706.3, IPC 2006.
01/19/2012 ROBERT SHERRY WATER REVIEW Approved
01/19/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
01/20/2012 MARTIN BROWN FIRE REVIEW Approved
02/03/2012 CPIERCE1 WWM REVIEW Needs Review
02/03/2012 CPIERCE1 ZONING REVIEW Needs Review