| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/30/2012 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 02/01/2012 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Several sheets have lettering sizes that do not comply with COT standards of 3/32" minimum for bot upper and lower case. Please revise those sheets not in complioance and resubmit. 2. At detail A/S2, note 5 calls for a W12 x 30 steel column whereas the calcs on page 15 calls for a 12 x 40. Please reconcile. 3. Please provide special inspection certifications as outlined on sheet S1. END OF REVIEW |
| 02/09/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |