Permit Number: T12CM00078
Parcel: 99999999A

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T12CM00078
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/12/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET D1.2; KEYNOTES: NOTES 7, 8, AND 9 DO NOT APPEAR ON THE PLAN. VERIFY.
2. SHEET D1.2; KEYNOTE 2: THE BUILDING DEMOLITION IS INCLUDED ON A SEPARATE PERMIT (T12BU00037). INCLUDE THIS NOTE.
3. SHEET A2.2; KEYNOTES: NOTES 6 AND 8 DO NOT APPEAR ON THE PLANS. VERIFY.
4. SHEET A5.2; KEYNOTES: NOTES 3 AND 4 DO NOT APPEAR ON THE PLANS. VERIFY.
5. SHEET A8.2; DETAILS 14 AND 15: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE.
6. SHEET S3.2; DETAIL 306: HOW BIG IS THE PEDESTAL? PROVIDE DIMENSIONS.
7. SHEET S3.2; DETAIL 301: SHOW THE HORIZONTAL REINFORCING IN THE NEW CONCRETE FOOTING.
8. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
01/12/2012 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
01/12/2012 LAITH ALSHAMI ENGINEERING REVIEW Approved
01/12/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
01/12/2012 STEVE SHIELDS ZONING REVIEW Denied PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Berkshire Village
T12CM00078
Building Plan (1st Review)

TRANSMITTAL DATE: January 12, 2012

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Sheet A2.2 Partial Plan 1 provide clear sidewalk dimensions between proposed building columns and existing buildings

3. Sheet A2.2 Partial Plan 1 provide a clear dimension from the proposed building columns and the north edge of sidewalk. If the dimension is less that 2'-6" wheel stop curbing will be required.

4. Sheet A2.2 Partial Plan 3 provide a clear sidewalk dimension from the 18" sono-tube bollards to the west edge of sidewalk. If the dimension is less that 6'-6" wheel stop curbing will be required.

5. Sheet A2.2 Partial Plan 3 Southwest corner provide a clear sidewalk dimension from the pop out to the west edge of sidewalk. If the dimension is less that 6'-6" wheel stop curbing will be required. 4'-0" minimum sidewalk is required.

6. Sheet A1.0 west end of the existing building does not match the new approved site plan.

7. Zoning will re-review the building plan on the next submittal to insure compliance with the approved development package. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
01/25/2012 CAGUILA1 FIRE REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
01/25/2012 CINDY AGUILAR OUT TO CUSTOMER Completed