Permit Number: T12CM00051
Parcel: 137055270

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM00051
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/10/2012 STEVE SHIELDS ZONING REVIEW Approved
01/10/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide calculations to show that the store has adequate ventilation per Section 403, IMC 2006.
2. Specify the minimum resistance (R-value) of the duct insulation to be used on this project. Reference: Section 503.2.7, IECC 2006, as amended by the City of Tucson.
3. Show the size, routing, and termination of the condensate drains. Reference: Section 307.2, IMC 2006 as amended by the City of Tucson and Section 814.0, UPC 2006.
01/10/2012 ERIC NEWCOMB ADA REVIEW Passed
01/10/2012 ROBERT SHERRY WATER REVIEW Approved
01/10/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
01/10/2012 PAUL MACHADO ENGINEERING REVIEW Approved
01/10/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a vacuum relief for storage-type water heaters located above any fixture outlets. Reference: Section 608.7, UPC 2006.
2. Provide upper terminal cleanouts on horizontal drainage pipes exceeding 5 feet in length (horizontal drain lines serving sinks require cleanouts regardless of length). Reference: Section 707.4, UPC 2006.
01/10/2012 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
01/11/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved T12CM00051

1. The main service is shown as 277/480 volts,then panel LA is shown as 120/208 volts, please correct this.
2. Commercial Submittal Requirements for the City of Tucson require a total load to be imposed on the main service which includes this space for a total, in order to verify the
service can contain added ampacity.
R T Majuta
Electrical Plan Review
PDSD City of Tucson
1/11/12
Ray.majuta@tucsonaz.gov
01/11/2012 MARTIN BROWN FIRE REVIEW Approved
01/25/2012 CPIERCE1 WWM REVIEW Needs Review