Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM00051
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/10/2012 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 01/10/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide calculations to show that the store has adequate ventilation per Section 403, IMC 2006. 2. Specify the minimum resistance (R-value) of the duct insulation to be used on this project. Reference: Section 503.2.7, IECC 2006, as amended by the City of Tucson. 3. Show the size, routing, and termination of the condensate drains. Reference: Section 307.2, IMC 2006 as amended by the City of Tucson and Section 814.0, UPC 2006. |
| 01/10/2012 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 01/10/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 01/10/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 01/10/2012 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
| 01/10/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide a vacuum relief for storage-type water heaters located above any fixture outlets. Reference: Section 608.7, UPC 2006. 2. Provide upper terminal cleanouts on horizontal drainage pipes exceeding 5 feet in length (horizontal drain lines serving sinks require cleanouts regardless of length). Reference: Section 707.4, UPC 2006. |
| 01/10/2012 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 01/11/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T12CM00051 1. The main service is shown as 277/480 volts,then panel LA is shown as 120/208 volts, please correct this. 2. Commercial Submittal Requirements for the City of Tucson require a total load to be imposed on the main service which includes this space for a total, in order to verify the service can contain added ampacity. R T Majuta Electrical Plan Review PDSD City of Tucson 1/11/12 Ray.majuta@tucsonaz.gov |
| 01/11/2012 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 01/25/2012 | CPIERCE1 | WWM | REVIEW | Needs Review |