Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T12CM00032
Parcel: 128102940

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM00032
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/12/2012 RONALD BROWN ADA REVIEW Passed
01/13/2012 LOREN MAKUS ENGINEERING REVIEW Approved
01/17/2012 CARL SCHULTZ FIRE REVIEW Denied On cover sheet need to show that fire alarm system is needed per IFC 907.2.2
01/18/2012 STEVE SHIELDS ZONING REVIEW Approved
01/23/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET TS1; CODE STUDY: VERIFY THE OCCUPANT LOAD FOR THE FIRST FLOOR CLASSROOM AREA. THE DRAWING INDICATES 282 OCCUPANTS, BUT THE PLAN ON SHEET A1 SHOWS SYSTEM FURNITURE FOR APPROXIMATELY 192 OCCUPANTS (NOT INCLUDING PROCTORS).
2. SHEET TS1; CODE STUDY: THE TOTAL OCCUPANT LOAD FOR THE FIRST FLOOR (310) IS NOT EQUAL TO THE SUM OF THE TWO AREAS (106 + 282). CLARIFY.
3. SHEETS A1, A1.1, A2, A2.1, A3, A3.1, A5 AND A5.1; KEY NOTES: KEY NOTE 6.6 REFERENCES DETAIL 5/A4. THIS IS INCORRECT. VERIFY.
4. SHEETS A1, A1.1, A2, A2.1, A3, A3.1, A5 AND A5.1; KEY NOTES: KEY NOTE 10.10 REFERENCES AN ADA GUIDELINE SECTION 4.30. USE A REFERENCE FOR ICC/ANSI A117.1-2003, SECTION 703. VERIFY.
5. SHEETS A1, A1.1, A2, A2.1, A3, A3.1, A5 AND A5.1; KEY NOTES: KEY NOTES 10.12 THROUGH 10.17 REFERENCE 1/A6. REVISE (NO SHEET A6).
6. SHEETS A1, A1.1, A2, A2.1, A3, A3.1, A5 AND A5.1; KEY NOTES: KEY NOTE 10.10 INDICATES THE SIGN TO BE MOUNTED 60' ABOVE F.F.E. REVISE.
7. SHEETS A3 AND A3.1; ROOM FINISH LEGEND: ADD W-E TO THE LEGEND.
8. SHEET A5; ELEVATIONS 2 AND 3: LOCATE THE TOILET PAPER DISPENSER (10.11) PER THE ICC/ANSI A117.1-2003, FIGURE 604.7. VERIFY.
9. SHEET A5; ELEVATION 7: PROVIDE ALL LOCATIONS AND LENGTHS OF GRAB BARS, LOCATION OF HAND SHOWER, AND SEAT DETAILS PER THE ICC/ANSI A117.1-2003, SECTION 608. VERIFY.
10. SHEET A5; ELEVATION 10: SINCE THE SINK IS IN AN ACCESSIBLE LOCATION, THE HEIGHT MUST FOLLOW THE REQUIREMENTS OF THE ICC/ANSI A117.1-2003, SECTION 606.3. VERIFY.
11. SHEET A5.1; ELEVATION 16: SINCE THE SINK IS IN AN ACCESSIBLE LOCATION, THE HEIGHT MUST FOLLOW THE REQUIREMENTS OF THE ICC/ANSI A117.1-2003, SECTION 606.3. VERIFY.
12. SHEET A5.1; ELEVATION 13A: PER THE IBC SECTION 1109.11, A PORTION OF THE RECEPTION COUNTER MUST ACCOMODATE ACCESSIBILITY REQUIREMENTS (34" MAXIMUM HEIGHT). VERIFY.
13. GENERAL: PROVIDE A SITE PLAN (NEW OR LAST APPROVED) WITH THIS SUBMITTAL.
14. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
01/25/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM00032
5441 E Williams Ci
TI Medical Offices

1. Panel UPSA (200amp) feeds Panel IS (100amps). The load shown on Panel IS is 134 amps ?

Ray Majuta
Electrical Pln Review
Ray.majuta@tucsonaz.gov
01/25/2012 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
02/02/2012 GERRY KOZIOL WWM REVIEW Approved
02/03/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
02/03/2012 ROBERT SHERRY WATER REVIEW Approved
02/03/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved