Review Details: COMMERCIAL - TI
Permit Number - T12CM00031
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/06/2012 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 01/06/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Needs Review | |
| 01/06/2012 | FRODRIG2 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 01/06/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 01/06/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEETS T3 (CODE STUDY), A1.0 (EQUIPMENT LIST), A2.0 (LIGHTING SCHEDULE), A3.0 (VARIOUS): THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE. 2. SHEET A1.0; LAYOUT FLOOR PLAN: THE SERVICE SINK AND DRINKING FOUNTAIN WERE NOT LOCATED ON THE PLAN. VERIFY. 3. SHEET A3.0; WEST BATHROOM: THE WATER CLOSET CLEARANCE MUST MEET CRITERIA OF THE ICC/ANSI A117.1-2003, FIGURE 604.3. VERIFY. 4. SHEET A3.0; DETAIL 1: BRACE THE WALL TO MEET THE CRITERIA OF THE 2006 IBC SECTION 1607.13. 5. GENERAL: LIST THE CODES USED FOR THIS PROJECT IN YOUR CODE ANALYSIS. 6. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 01/06/2012 | FRODRIG2 | WWM | REVIEW | Needs Review | |
| 01/06/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
| 01/06/2012 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 01/06/2012 | MARTIN BROWN | FIRE | REVIEW | Denied | Note 12 on sheet S.1 indicates new kitchen hood. Please define if type 1 or type 2 and what kind of appliances will be installed in kitchen. |
| 01/06/2012 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 01/06/2012 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |