Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T12CM00027
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/15/2012 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 02/29/2012 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 03/02/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Revise Specification 220700, Section 2.2, A, (1) to comply with the requirements of Section 504.5, IECC 2006. The requirement is 1-inch of insulation having a conductivity not exceeding 0.27 BTU per inch per hour per foot squared per degree Fahrenheit. |
| 03/06/2012 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 03/15/2012 | GERRY KOZIOL | WWM | REVIEW | Approved |